Effect of unsymmetrical faults on distribution lines with different line X/R ratios and voltage restoration using DVR with Space vector control
Author :
Sreelatha, P.N.K. ; Praveen, J. ; Kamaraju, V.
Author_Institution :
JNTUH, Hyderabad, India
fYear :
2012
fDate :
21-22 March 2012
Firstpage :
92
Lastpage :
97
Abstract :
Very often in distribution systems many small loads of the order of 100KVA or less are fed from same feeder. A fault at one load drastically affects the loads even at far end. Here the effect of L-G and L-L faults followed by an Open conductor fault (fuse blow off in one phase) at the remote load point is presented for different feeder X/R ratios. The restoration of supply voltages using a DVR (with Space vector control) at the desired load point is studied.
Keywords :
power distribution control; power distribution faults; power distribution lines; DVR; L-G faults; L-L faults; apparent power 100 kVA; distribution line unsymmetrical fault effect; distribution systems; feeder X-R ratios; line X-R ratios; open conductor fault; remote load point; space vector control; supply voltage restoration; voltage restoration; Space vector pulse width modulation; Distribution feeders; Dynamic voltage restorer; Space vector control; Voltage sag; faults; power quality;