Abstract
This paper describes the application of a permissive overreaching transfer trip (POTT) system to protect a double circuit transmission line for which single pole tripping and reclosing was required to ensure power system stability. Application of the advanced relay-to-relay logic communications (a.k.a. mirrored bit logic) in the numerical relays provide a solution to the cross-country fault problem. This new technology also reduces the overall complexity and equipment costs
Keywords
power transmission lines; 235 kV; 65 mile; cross-country fault problem; double circuit transmission line; equipment costs reduction; mirrored bit logic; numerical relays; permissive overreaching transfer trip system; power system stability; relay-to-relay logic communications; single pole reclosing; single pole tripping; transmission line protection;