Abstract :
Conventional fault location systems which use one-terminal AC voltages and currents are difficult to apply to multi-terminal power systems. This paper discusses a new fault location system for multi-terminal single transmission lines. Asynchronous sampling at each terminal is preferred in order to simplify the transmission equipment and an algorithm for synchronizing the asynchronous sampling data is presented. Another algorithm is presented which converts the original multi-terminal power system by progressive conversion to a system with one fewer terminals to arrive at a 2-terminal system containing the fault. An effective fault locating system can be constructed by combining these algorithms with existing reactive power locating operations. EMTP simulation results are presented
Keywords :
digital simulation; fault location; power system analysis computing; power system protection; power transmission lines; software packages; synchronisation; transmission networks; AC current; AC voltage; EMTP; algorithm; asynchronous sampling; computer simulation; fault location; multi-terminal power systems; single transmission lines; synchronization; Communication equipment; Digital relays; Fault location; Impedance; Power transmission lines; Reactive power; Sampling methods; Transmission line matrix methods; Transmission lines; Voltage;
fLanguage :
English
Publisher :
ieee
Conference_Titel :
Transmission and Distribution Conference, 1994., Proceedings of the 1994 IEEE Power Engineering Society
Conference_Location :
Chicago, IL
Print_ISBN :
0-7803-1883-8
Type :
conf
DOI :
10.1109/TDC.1994.328390
Filename :
328390
Link To Document :
بازگشت