Ampacity calculations for mixed underground cable systems in the same ductbank
Author :
Kansog, Jurgen O C ; Brown, Matthew T.
Author_Institution :
Ebasco Div., Raytheon Eng. & Constructors, Lyndhurst, NJ, USA
fYear :
1994
fDate :
10-15 Apr 1994
Firstpage :
535
Lastpage :
543
Abstract :
The steady state ampacity is calculated for mixed electric power underground cable circuits in a single trench or ductbank. The methodology presented in this paper can be applied to any practical number of balanced, three phase circuits (each in trefoil, pipe or conduit) of different voltage classes, cable sizes, load currents and cable systems located anywhere within a single trench or ductbank. The different thermal resistivities of the backfill or ductbank and the surrounding soil are taken into consideration. A practical example for 10 circuits in a trench is provided
Keywords :
electric conduits; power cables; soil; thermal conductivity; underground cables; backfill; cable size; conduit; ductbank; load current; mixed power underground cable circuits; pipe; soil; steady state ampacity; thermal resistivity; three phase; trefoil; trench; voltage class; Cables; Circuits; Conductivity; Conductors; Interference; Soil; Steady-state; Temperature; Thermal loading; Thermal resistance;