• DocumentCode
    2184601
  • Title

    Rodbed grounding resistances from the single driven rod resistance the “F” multiplication factor

  • Author

    Elsherbiny, M.M. ; Salama, M.M.A. ; Chow, Y.L.

  • Author_Institution
    Dept. of Electr. & Comput. Eng., Waterloo Univ., Ont., Canada
  • Volume
    2
  • fYear
    1995
  • fDate
    8-12 Oct 1995
  • Firstpage
    1749
  • Abstract
    A novel approach is used to derive an accurate and simple analytical formula to calculate the resistance of a rodbed in a two-layer earth. First, we use the IEEE-standard formula for a single driven rod resistance and multiply it by a factor “F” to obtain the resistance of the rodbed. This “F” factor is derived based on the analytical moment method and duality concept. Second, for a two-layer earth we modify the IEEE-standard formula for a single rod to include the effects of the infinite series of images. Upper and lower rodbed parts resistances are calculated and combined to obtain the total resistance of the rodbed using the synthetic asymptote technique. The results of the formula are compared with the published detailed moment method results, the agreement is very good
  • Keywords
    duality (mathematics); earth electrodes; electric resistance; F multiplication factor; IEEE-standard formula; duality concept; rodbed grounding resistances; single driven rod resistance; synthetic asymptote technique; two-layer earth; Conductivity; Design engineering; Earth; Electric resistance; Grounding; Image analysis; Moment methods; Power engineering and energy; Power system reliability; Reliability engineering;
  • fLanguage
    English
  • Publisher
    ieee
  • Conference_Titel
    Industry Applications Conference, 1995. Thirtieth IAS Annual Meeting, IAS '95., Conference Record of the 1995 IEEE
  • Conference_Location
    Orlando, FL
  • ISSN
    0197-2618
  • Print_ISBN
    0-7803-3008-0
  • Type

    conf

  • DOI
    10.1109/IAS.1995.530517
  • Filename
    530517