  • Abstract
    A mobile calibration system for in-situ calibration of voltage transformers is analysed with respect to measuring uncertainty under field conditions. The total basic uncertainty is better than /spl plusmn/0.015% respectively /spl plusmn/0.3 mrad. The system has been used to calibrate 570 capacitor voltage transformers.<>
  • Keywords
    automatic test equipment; bridge instruments; calibration; high-voltage techniques; measurement errors; power transformers; transformer testing; Swedish National Grid; capacitor voltage transformers; high voltage transformers; insitu calibration; measuring uncertainty; mobile calibration; Calibration; Capacitors; Electrical resistance measurement; Electromagnetic measurements; Instruments; Magnetic field measurement; Measurement uncertainty; Optical fiber cables; Stability; Voltage transformers;