• DocumentCode
    2194811
  • Title

    A new modified PQ theory used for reactive power and current harmonic compensation

  • Author

    Benghanem, M. ; Alradadi, E.A. ; Draou, A.

  • Author_Institution
    Dept. of Electrotechnics, Oran Univ. of Sci. & Technol.
  • fYear
    2006
  • fDate
    23-26 May 2006
  • Firstpage
    1306
  • Lastpage
    1309
  • Abstract
    This paper presents the performance analysis of an active power filter (APF) using a three-level neutral point-clamped voltage source inverter. This APF can effectively compensate current harmonics and reactive power. The operating principles and the generation method of reference currents using modified classical PQ instantaneous method are presented. This modified method is suitable for the case of voltages contaminated by harmonics in a three-phase power system. The dynamic behaviour of the system is analysed using Simulink with SimPower Systems toolbox through a set of simulation tests. The results obtained may lead to a correct design of a robust controller for current harmonics and reactive power applications
  • Keywords
    active filters; control system synthesis; invertors; power harmonic filters; robust control; static VAr compensators; SimPower Systems toolbox; active power filter; current harmonic compensation; current harmonics compensation; reactive power; robust controller design; three-level neutral point-clamped voltage source inverter; three-phase power system; Active filters; Inverters; Performance analysis; Power harmonic filters; Power system analysis computing; Power system dynamics; Power system harmonics; Power system simulation; Reactive power; Voltage;
  • fLanguage
    English
  • Publisher
    ieee
  • Conference_Titel
    Power Electronics, Electrical Drives, Automation and Motion, 2006. SPEEDAM 2006. International Symposium on
  • Conference_Location
    Taormina
  • Print_ISBN
    1-4244-0193-3
  • Type

    conf

  • DOI
    10.1109/SPEEDAM.2006.1649969
  • Filename
    1649969