Abstract :
The measurement of breakdown of vacuum interrupters after arcing by applying a DC recovery voltage is conducted to study the multiple restrike phenomena in capacitor switching. It is found that the breakdown probability increases with the arcing current until at a specific current value when the full conditioning effect is reached. For practically eliminating the occurrence of multiple restrike phenomena this specific current can be used as the conditioning current so as to accelerate the conditioning process. Such a method is called the enhanced conditioning method because the conditioning current and voltage are much higher than the rated values
Keywords :
circuit-breaking arcs; power capacitors; restriking voltage; switching; vacuum breakdown; vacuum interrupters; DC recovery voltage; arcing current; breakdown probability; capacitor switching; conditioning current; conditioning effects; conditioning voltage; enhanced conditioning method; multiple restrike phenomena; vacuum interrupter; vacuum interrupters breakdown measurement; Breakdown voltage; Capacitors; Circuits; Conducting materials; Contacts; Dielectrics and electrical insulation; Electric breakdown; Interrupters; Switches; Vacuum arcs;
fLanguage :
English
Publisher :
ieee
Conference_Titel :
Discharges and Electrical Insulation in Vacuum, 1996. Proceedings. ISDEIV., XVIIth International Symposium on
Conference_Location :
Berkeley, CA
Print_ISBN :
0-7803-2906-6
Type :
conf
DOI :
10.1109/DEIV.1996.545374
Filename :
545374
Link To Document :
بازگشت