Abstract :
A detection system for cables damaged by lightning stroke is developed using videos obtained from an aerial inspection of transmission lines. The system detects arc marks and cut wires. Arc marks are detected by statistical analysis of the brightness of a cable image. Cut wires are detected by comparing the contour of the cable, which was obtained with a video camera, with its ideal shape. The developed system was applied to videos of 20 cases, which included a damaged cable. The total number of images was 6000. The system could detect all types of cable damage. In 97.8% of images, the system worked well, making it suitable for aid in the inspection of transmission lines.
Keywords :
fault diagnosis; image recognition; inspection; lightning; power cables; power transmission lines; statistical analysis; video cameras; arc marks; cable image brightness; damaged cables; fault detection system; image processing; image recognition; lightning stroke; statistical analysis; transmission lines; video camera; Brightness; Cables; Inspection; Lightning; Power system reliability; Power transmission lines; Shape; Transmission lines; Video recording; Wires;
fLanguage :
English
Publisher :
ieee
Conference_Titel :
Power Engineering Society General Meeting, 2004. IEEE
Conference_Location :
Denver, CO
Print_ISBN :
0-7803-8465-2
Type :
conf
DOI :
10.1109/PES.2004.1373201
Filename :
1373201
Link To Document :
بازگشت