DocumentCode :
2205158
Title :
Large-scale survey of furanic compounds in operating transformers and implications for estimating service life
Author :
Sans, John R. ; Bilgin, K. Muge ; Kelly, Joseph J.
Author_Institution :
S.D. Myers Inc., Tallmadge, OH, USA
Volume :
2
fYear :
1998
fDate :
7-10 Jun 1998
Firstpage :
543
Abstract :
The concentration of furanic compounds in the dielectric fluid of a transformer is a good indicator of the condition of the cellulosic materials such as paper, pressboard, and cotton materials used both as electrical insulation and as mechanical support. The condition of the cellulosic materials is vital, because those materials are the limiting factor on the life of a transformer. Over the last three years, the lab at S.D. Myers has conducted a massive survey of the concentration of furanic compounds in the dielectric fluid of operating transformers. The Myers data base now contains more than 15,000 test results on dielectric fluids, including mineral oil; silicone, PCB-askarel, high fire-point oil, and perchloroethylene. The furan test is especially valuable for the PCB-askarel units, because the dissolved combustible gas test is not very useful for such units. The furanic compounds were measured with a high performance liquid chromatograph (HPLC) per ASTM Method D 5837. Due to the massive furan survey data available, it is now possible to interpret furan test results actuarially. This approach works best for the mineral oil transformers with more than 12,000 furan test results as of January 1, 1998
Keywords :
chromatography; insulation testing; power transformer insulation; reliability; transformer oil; PCB-askarel; cellulosic material condition; dielectric fluid; electrical insulation; furanic compounds; high fire-point oil; liquid chromatograph; mineral oil; operating transformers; perchloroethylene; service life; silicone; Conducting materials; Cotton; Dielectric materials; Dielectric measurements; Dielectrics and electrical insulation; Large-scale systems; Minerals; Petroleum; Power transformer insulation; Testing;
fLanguage :
English
Publisher :
ieee
Conference_Titel :
Electrical Insulation, 1998. Conference Record of the 1998 IEEE International Symposium on
Conference_Location :
Arlington, VA
ISSN :
1089-084X
Print_ISBN :
0-7803-4927-X
Type :
conf
DOI :
10.1109/ELINSL.1998.694852
Filename :
694852
Link To Document :
بازگشت