Title :
Correction of Under-reaching in Twin circuit Parallel Overhead Lines without Residual Current input from the Parallel Line
Author :
Abdullah, Mohd Faris Bin ; Mukerj, R.N. ; Ramachandaramurthy, Vigna K.
Author_Institution :
TNB Transmission, Tenaga Nasional Berhad
Abstract :
Mutual coupling poses one of the most difficult problems witnessed during single phase to earth fault, in transmission line protection. In lines, on multiple circuit towers or on the same right of way, the zero-sequence circuits of the lines get mutually coupled causing an error in the apparent impedance seen by the relay. This causes the distance protection relay at one end of the faulty line to over-reach while the one at the other end to under-reach. Also, incorrect sensing of the ground fault due to zero-sequence voltage inversion caused by mutual coupling in the zero-sequence network may lead to false trip of the neighbouring healthy line. This paper presents a non-iterative microprocessor based algorithm, not requiring residual current measurement from the parallel circuit, for computing fault distance and zero sequence compensation in basic distance relaying scheme
Keywords :
earthing; poles and towers; power overhead lines; power transmission faults; power transmission protection; relay protection; apparent impedance; distance protection relay; earth fault; multiple circuit towers; mutual coupling; noniterative microprocessor; transmission line protection; twin circuit parallel overhead lines; zero-sequence circuits; zero-sequence voltage inversion; Circuit faults; Coupling circuits; Earth; Impedance; Microprocessors; Mutual coupling; Poles and towers; Power system protection; Protective relaying; Voltage;
Conference_Titel :
TENCON 2006. 2006 IEEE Region 10 Conference
Conference_Location :
Hong Kong
Print_ISBN :
1-4244-0548-3
Electronic_ISBN :
1-4244-0549-1
DOI :
10.1109/TENCON.2006.343910