Title :
An Approach to Determine the Health Index of Power Transformers
Author :
Naderian, A. ; Cress, S. ; Piercy, R. ; Wang, F. ; Service, J.
Author_Institution :
Transm. & Distrib. Technol., Kinectrics Inc., Toronto, ON
Abstract :
This paper describes a realistic health index formulation method for power transformers using readily available data. The method considers practical limitations on obtaining data, and the possible constraints on the parameters. It also utilizes IEC, IEEE, and CIGRE criteria for condition parameters. This Health Index calculation considers not only typical test results such as dissolved gas analysis (DGA), oil quality, furan, and power factor, but also other parameters such as tap changer and bushing condition, physical observations, load history, maintenance work orders, and age. The calculation includes condition ratings, weighting factors, and assigned scores for specific condition parameters. By using a multi-criteria analysis approach, the method combines the various factors into a condition-based health index.
Keywords :
IEC standards; IEEE standards; condition monitoring; power factor; power transformer testing; CIGRE criteria; IEC criteria; IEEE criteria; condition ratings; dissolved gas analysis; maintenance work orders; oil quality; power factor; power transformer testing; transformer health index; weighting factors; Circuit testing; Dissolved gas analysis; History; Insulation testing; Insulators; Investments; Oil insulation; Petroleum; Power transformer insulation; Power transformers;
Conference_Titel :
Electrical Insulation, 2008. ISEI 2008. Conference Record of the 2008 IEEE International Symposium on
Conference_Location :
Vancouver, BC
Print_ISBN :
978-1-4244-2091-9
Electronic_ISBN :
1089-084X
DOI :
10.1109/ELINSL.2008.4570308