• DocumentCode
    2213487
  • Title

    Power-Factor Fluctuation of Directly Water-Cooled Generator-Bar after Water-Penetration inside the Groundwall Insulation

  • Author

    Naghashan, M.R. ; Farrokhi, M.

  • Author_Institution
    Power & Water Univ. of Technol., Tehran
  • fYear
    2008
  • fDate
    9-12 June 2008
  • Firstpage
    273
  • Lastpage
    275
  • Abstract
    A directly water-cooled generator-bar with laboratory tests is presented in this paper. A leak point is made inside the groundwall insulation of the bar. The cooling water migrates along the generator bar through insulation delamination and interstices between copper strands. The speed of water flow inside the insulation is measured during the test period. Capacitance and power-factor mapping tests are carried out along the generator-bar length. The results show that the capacitance and dissipation factor are fluctuated reversely over a period of time. Dissipation factor variation of the generator-bar is higher than the capacitance variation.
  • Keywords
    bars; capacitance; cooling; electric generators; insulation testing; machine insulation; machine testing; power factor; velocity measurement; capacitance tests; direct water-cooled generator-bar; dissipation factor variation; flow speed measurement; groundwall insulation test; insulation delamination; power-factor fluctuation; power-factor mapping tests; water-penetration; Capacitance; Cooling; Copper; Delamination; Fluctuations; Fluid flow measurement; Insulation; Laboratories; Power generation; Testing;
  • fLanguage
    English
  • Publisher
    ieee
  • Conference_Titel
    Electrical Insulation, 2008. ISEI 2008. Conference Record of the 2008 IEEE International Symposium on
  • Conference_Location
    Vancouver, BC
  • ISSN
    1089-084X
  • Print_ISBN
    978-1-4244-2091-9
  • Electronic_ISBN
    1089-084X
  • Type

    conf

  • DOI
    10.1109/ELINSL.2008.4570327
  • Filename
    4570327