DocumentCode :
2214433
Title :
Breakdown testing of standard insulation materials with high frequency voltages for an assessment of stresses, generated by repetitive pulses
Author :
Nagel, M. ; Otte, P. ; Leibfried, T.
Author_Institution :
Inst. of Electr. Energy Syst. & High Voltage Technol., Univ. of Karlsruhe, Karlsruhe
fYear :
2008
fDate :
9-12 June 2008
Firstpage :
466
Lastpage :
469
Abstract :
Despite the classic stresses on insulation systems, repetitive voltage pulses are more and more present in modern power systems. Their influence is yet quite unknown. Considering the large slew and repetition rates of HVDC valves with voltage-sourced converters, high frequency noise is generated and subjected to the insulation systems, e.g. oil and cellulose, used in transformers. For an assessment of the material properties of insulating materials, the breakdown strength is the most basic value needed. In order to be able to obtain those values for frequencies up to 400 kHz, with reasonable gap distances, an amplitude of 100 kV is crucial. The voltage should additionally be increasable from zero up to the breakdown, imitating the standard 50/60 Hz AC testing. In that matter, a test system was built for generating such kind of signals. For implementation a series resonance circuit was constructed, which is excited by a frequency variable inverter at the resonance frequency. Of special importance is thereby the optimization of the circuit itself to minimize losses and to increase the amplitude reachable. Not only the reactor was therefore specially designed, but the capacitive parts as well. Limiting for the last part, when e.g. thinking of standard test vessels for transformer-oil, is a minimum capacity needed for proper operation of the resonance circuit. Testing of insulation materials, concerning the breakdown strength against the high frequency voltages was done subsequently, as well as a comparison with standard power frequency values. Different influences on their behavior, like the moisture content of transformer-oil were investigated as well.
Keywords :
HVDC power convertors; electric breakdown; insulation testing; power systems; transformer oil; HVDC valves; breakdown testing; frequency variable inverter; high frequency voltages; power systems; repetitive voltage pulses; series resonance circuit; standard insulation materials; stress assessment; transformer-oil; voltage-sourced converters; Breakdown voltage; Circuit testing; Frequency; Insulation testing; Materials testing; Oil insulation; Power transformer insulation; Pulse generation; Pulse power systems; Stress;
fLanguage :
English
Publisher :
ieee
Conference_Titel :
Electrical Insulation, 2008. ISEI 2008. Conference Record of the 2008 IEEE International Symposium on
Conference_Location :
Vancouver, BC
ISSN :
1089-084X
Print_ISBN :
978-1-4244-2091-9
Electronic_ISBN :
1089-084X
Type :
conf
DOI :
10.1109/ELINSL.2008.4570374
Filename :
4570374
Link To Document :