Abstract
The injection of reactive power with STATCOM for the control of load bus voltage of a radial system at various locations is examined. The STATCOM which consists of a fixed capacitor bank and a three phase single level voltage source inverter is defined in brief. Also highlighted are new concepts of variable pulse widths and delay angles on the effectiveness of STATCOM for loads such as induction machines and synchronous machines illustrated by simulation. Results suggest, for the load bus voltage to remain within statuary limits, the cost of inverter per reactive power injection is more economical at the load bus
Keywords
capacitor storage; flexible AC transmission systems; invertors; load (electric); power system control; reactive power; voltage control; FACTS devices; delay angles; fixed capacitor bank; induction machines; load bus voltage; load bus voltage control; optimum location dependency; radial system; reactive power demand; reactive power injection; simulation; synchronous machines; three phase single level voltage source inverter; variable pulse widths; Automatic voltage control; Capacitors; Control systems; Delay effects; Induction machines; Pulse width modulation inverters; Reactive power; Reactive power control; Space vector pulse width modulation; Voltage control;
fLanguage
English
Publisher
ieee
Conference_Titel
Electric Utility Deregulation and Restructuring and Power Technologies, 2000. Proceedings. DRPT 2000. International Conference on
Conference_Location
London
Print_ISBN
0-7803-5902-X
Type
conf
DOI
10.1109/DRPT.2000.855631
Filename
855631
Link To Document