DocumentCode
2225819
Title
Axial magnetic field interrupters in autorecloser applications
Author
Bestel, E. Fred ; Stoving, Paul N.
Author_Institution
Cooper Power Syst., Kyle Distribution Switchgear, South Wilwaukee, WI, USA
Volume
2
fYear
1996
fDate
21-26 Jul 1996
Firstpage
1045
Abstract
Application of vacuum interruption in distribution switchgear, especially in autoreclosers, which have uniquely high demands on vacuum fault interrupters, are discussed. The fast open-close-open sequence and its associated highly asymmetrical waveforms are some of the difficulties encountered. The authors present their solution to these problems in the form of an economical axial magnetic field interrupter that realizes current densities of up to 1.68 kA/cm2-the most efficient axial magnetic interrupter that is in production today. Actual design test data per ANSI C37.60 is shown
Keywords
distribution networks; magnetic fields; power system protection; vacuum interrupters; ANSI C37.60 standard; asymmetrical waveforms; autoreclosers; axial magnetic field interrupters; current densities; design test data; distribution switchgear; open-close-open sequence; vacuum fault interrupters; vacuum interruption; Circuit breakers; Circuit testing; Contacts; Interrupters; Magnetic fields; Magnetic switching; Power system reliability; Switches; Switchgear; Vacuum systems;
fLanguage
English
Publisher
ieee
Conference_Titel
Discharges and Electrical Insulation in Vacuum, 1996. Proceedings. ISDEIV., XVIIth International Symposium on
Conference_Location
Berkeley, CA
Print_ISBN
0-7803-2906-6
Type
conf
DOI
10.1109/DEIV.1996.545525
Filename
545525
Link To Document