Abstract :
The root causes of underground distribution medium voltage cable faults are water penetration into insulation layer and stress enhancement on semi-conductive layers. Accordingly, it is needed to improve the waterproof performance of jacket materials and the structure of power cables for extending lifetime and preventing failure. We uses non-flaming polyethylene materials instead of PVC(polyvinyl chloride) as a outer jacket material and encapsulating structure. We also use super smooth class material as a inner semi-conductive layer. The newly developed cables have improved in AC breakdown voltage after ageing tests.
Keywords :
ageing; plastics; power system faults; underground cables; underground distribution systems; ageing tests; encapsulating structure; improved AC breakdown voltage; improved underground distribution power cables; jacket materials; medium voltage cable faults; nonflaming polyethylene materials; semiconductive layer; smooth class material; stress enhancement; water penetration; waterproof performance; Aging; Cable insulation; Cable shielding; Medium voltage; Polyethylene; Power cable insulation; Power cables; Stress; Testing; Underground power cables;