DocumentCode :
2244573
Title :
Slot discharge mechanisms in high voltage rotating machines
Author :
Edwards, D.G.
Author_Institution :
Robert Gordon Univ., Aberdeen, UK
fYear :
1993
fDate :
28-30 Sep 1993
Firstpage :
113
Lastpage :
114
Abstract :
High voltage stator winding insulation in modern rotating machines has a high degree of resistance to erosion by partial discharge but on-line monitoring of partial discharge activity can give useful early warning of physical degradation processes which could lead to premature insulation failure if not detected in time. Well defined changes in slot discharge pulse pattern have been shown to characterise the progression of physical damage due to movement of coil sides in the stator slots
Keywords :
insulation testing; machine insulation; machine testing; partial discharges; stators; coil; degradation; erosion; high voltage rotating machines; insulation failure; on-line monitoring; partial discharge; pulse pattern; slot discharge; stator winding;