• DocumentCode
    2248322
  • Title

    Performance of average current mode controlled PWM UPS inverter with high crest factor load

  • Author

    Fraser, M.E. ; Manning, C.D.

  • Author_Institution
    Loughborough Univ. of Technol., UK
  • fYear
    1994
  • fDate
    26-28 Oct 1994
  • Firstpage
    661
  • Lastpage
    667
  • Abstract
    This paper highlights the problems encountered when attempting to supply a high crest factor load from a UPS inverter. Inverter voltage control using an inner loop consisting of an average current mode controller and an outer loop is investigated. The choice of parameters, filter components and compensators, are discussed. Simulation results show the steady state and dynamic performance of the inverter. The addition of load current feedforward can cause the system to become unstable and is explained with the aid of simplified control models. The inverter under consideration is rated at 30 kVA with a PWM switching frequency of 15 kHz
  • Keywords
    PWM invertors; circuit analysis computing; circuit stability; control system analysis computing; digital simulation; electric current control; feedforward; load (electric); power engineering computing; uninterruptible power supplies; voltage control; 15 kHz; 30 kVA; PWM UPS inverter; average current mode control; compensators; computer simulation; dynamic performance; feedforward; filter components; high crest factor load; inner loop; instability; outer loop; parameters; steady state performance; switching frequency; voltage control;
  • fLanguage
    English
  • Publisher
    iet
  • Conference_Titel
    Power Electronics and Variable-Speed Drives, 1994. Fifth International Conference on
  • Conference_Location
    London
  • Type

    conf

  • DOI
    10.1049/cp:19941043
  • Filename
    341631