DocumentCode
2255935
Title
A single monitor method for voltage sag source location using Hilbert Huang transform
Author
Wong Ling Ai ; Shareef, Hussain ; Ibrahim, Ahmed A.
Author_Institution
Dept. of Electr., Electron. & Syst. Eng., UKM Bandar, BaruBangi, Malaysia
fYear
2012
fDate
12-14 Dec. 2012
Firstpage
374
Lastpage
379
Abstract
This paper introduces a method for voltage sag source location based on Hilbert Huang transformed monitored current signal. Unlike the traditional method, the proposed method first transforms the recorded current during the sag event to obtain frequency-time plot (Hilbert spectra) and IMF plot before the location of voltage sag source is determined. Then based on the change in frequency and IMF the relative location of voltage sag source is obtained. The effectiveness of the proposed method has been verified through simulation on 20 bus system and by comparing with an existing S-Transform based method. The results show that the presented method can determine the location of voltage sag source correctly.
Keywords
Hilbert transforms; electric current measurement; power supply quality; power system measurement; signal processing; Hilbert spectra; Hilbert-Huang transform; IMF plot; S-transform based method; current signal monitoring; frequency-time plot; single monitor method; voltage sag source location; Hilbert Huang Transform; power quality; signal processing; voltage sags;
fLanguage
English
Publisher
ieee
Conference_Titel
IPEC, 2012 Conference on Power & Energy
Conference_Location
Ho Chi Minh City
Type
conf
DOI
10.1109/ASSCC.2012.6523296
Filename
6523296
Link To Document