DocumentCode :
2259696
Title :
Effects of temperature on water tree initiation and propagation at equivalent AC frequency
Author :
Uehara, Hideyuki ; Kudo, K. ; Ishikawa, Yozo ; Kanekawa, Teruo ; Tsuboi, Y. ; Yoshimitsu, Tetsuo
Author_Institution :
Kanto Gakuin Univ., Yokohama, Japan
fYear :
2011
fDate :
6-10 Sept. 2011
Firstpage :
217
Lastpage :
220
Abstract :
Water treeing occurs when an ac voltage is applied to an electrical insulation system such as those in power cables and power apparatus. From a practical viewpoint, research on water treeing has mostly been performed under the application of a high-frequency ac voltage. However, in recent years, power cables and power apparatus have also been used under dc voltage application owing to progress in inverter technology. The use of rotating electrical machines with an inverter has become widespread owing to their contribution to the prevention of global warming, high effectiveness and the reduced maintenance required. In an underwater motor driven by the voltage of an inverter, it is necessary to consider the water treeing of the motor insulation and the cable insulation connected to the drive board. Up to now, we have performed accelerated deterioration tests at the inverter carrier frequency of 500Hz. However, in the case of an inverter waveform, an accelerated deterioration test cannot be performed because the inverter waveform becomes markedly different from that of an actual machine when the basic frequency is increased. In this paper, we report the development of a new water electrode test method and the investigation of the effects of temperature on water tree initiation and propagation utilizing an equivalent ac frequency of 50Hz. We found that a water tree was initiated within two weeks even at the basic frequency of 50Hz. Furthermore, we compared the test results obtained at 500Hz and 50Hz at different temperatures.
Keywords :
XLPE insulation; insulation testing; life testing; machine insulation; trees (electrical); accelerated deterioration tests; cable insulation; drive board; electrical insulation system; equivalent AC frequency; frequency 50 Hz; frequency 500 Hz; inverter waveform; motor insulation; power apparatus; power cables; temperature effects; tree propagation; underwater motor; water tree initiation; Electrodes; Inverters; Life estimation; Needles; Shape; Temperature measurement; Trees - insulation; equivalent ac frequency; new water electrode; temperature; water tree; waveform;
fLanguage :
English
Publisher :
ieee
Conference_Titel :
Electrical Insulating Materials (ISEIM), Proceedings of 2011 International Conference on
Conference_Location :
Kyoto
Print_ISBN :
978-4-88686-074-3
Type :
conf
DOI :
10.1109/ISEIM.2011.6826388
Filename :
6826388