Abstract :
This paper describes measurement of the low frequency amplitude and phase response for current signals on a distribution network associated with a 6 MW co-generation plant. The channel includes an LV/MV (240 V/22 kV) distribution transformer. Measurements were made between 100 Hz and 3 kHz and a parametric model is derived. Noise measurements for the channel are also described and the maximum information capacity (Shannon limit) of this "through transformer" channel, when used with practical signal levels, is estimated.
Keywords :
carrier transmission on power lines; channel capacity; cogeneration; distribution networks; power transformers; channel modelling; co-generation plant; distribution network; frequency 100 Hz; frequency 3 kHz; low frequency amplitude measurement; maximum information capacity; phase response; power 6 MW; power-line communication; transformer; Information technology; Channel model; Information capacity; Power-Line;