Title :
Network transient responses to varying HVAC line length along a HVDC transmission corridor
Author :
Oyedokun, D.T. ; Folly, K.A.
Author_Institution :
Dept. of Electr. Eng., Univ. of Cape Town, Cape Town, South Africa
Abstract :
This paper deals with the complex network transient responses to AC and DC faults in transmission network with a fixed HVDC transmission line and varying HVAC transmission lines. The rotor angle stability and management of the reactive power are investigated in order to define the network transient responses. The simulations are carried out using a multi machine power system model using DigSILENT software package. The results indicated that the network transient response cannot be generalized but defined into two separate categories namely AC and DC. During the HVDC transmission line fault, the overall rotor angle stability of the is enhanced with the increase in length of the HVAC transmission line.
Keywords :
HVDC power transmission; power system simulation; power transmission faults; power transmission lines; reactive power; rotors; software packages; transient response; AC faults; DC faults; DigSILENT software package; HVDC transmission corridor; HVDC transmission line fault; fixed HVDC transmission line; multimachine power system model; network transient response; reactive power management; rotor angle stability; transmission network; varying HVAC line length; Circuit faults; HVDC transmission; Power system stability; Power transmission lines; Reactive power; Rectifiers; Rotors; HVAC; HVDC; Hybrid HVAC-HVDC transient stability; rotor angle; voltage dip;
Conference_Titel :
AFRICON, 2011
Conference_Location :
Livingstone
Print_ISBN :
978-1-61284-992-8
DOI :
10.1109/AFRCON.2011.6072157