Fault simulation studies of single-line faults in a delta-delta connected distribution system
Author :
Momoh, J.A. ; Dias, L.G. ; Thor, T. ; Laird, D.N.
Author_Institution :
Dept. of Electr. Eng., Howard Univ., Washington, DC, USA
fYear :
1993
fDate :
16-18 Aug 1993
Firstpage :
377
Abstract :
Single-line faults in delta-delta connected distribution systems normally draw very low fault currents and cannot be detected by the usual overcurrent protective devices. The ground alarm relays that are used in this type of system can detect most ground faults but can neither identify the faulty feeder nor classify the fault type, nor detect open conductor faults. This paper describes an exhaustive simulation study, which will provide criteria for the detection and identification of single-line faults in a delta-delta connected distribution system. The conclusion is, that for single-line faults with no intermittent contact, criteria can be obtained, which can be used for detection and identification of single-line faults (including open conductor faults)
Keywords :
digital simulation; distribution networks; electrical faults; identification; combined faults; delta-delta connected distribution system; fault currents; fault simulation; ground alarm relays; ground faults; open conductor faults; overcurrent protective devices; series fault; shunt fault; single-line faults; Capacitance; Conductors; Electrical fault detection; Fault currents; Fault detection; Fault diagnosis; Impedance; Power system faults; Power system protection; Protective relaying;
fLanguage :
English
Publisher :
ieee
Conference_Titel :
Circuits and Systems, 1993., Proceedings of the 36th Midwest Symposium on
Conference_Location :
Detroit, MI
Print_ISBN :
0-7803-1760-2
Type :
conf
DOI :
10.1109/MWSCAS.1993.343031
Filename :
343031
Link To Document :
بازگشت