Adverse increase in generator terminal voltage and reactive power transients caused by power system stabilizers
Author :
Ferraz, Julio Cesar Rezende ; Zeni, N. ; Taranto, Glauco N.
Author_Institution :
COPPE/UFRJ - CP 68564, Rio de Janeiro
Volume :
2
fYear :
2002
fDate :
2002
Firstpage :
747
Abstract :
This paper studies the adverse impact on the transient performance of both generator terminal voltage and reactive power output caused by power system stabilizers (PSS). The analysis of the zeros of a transfer function different from that of the stabilization loop provides a better understanding of the adverse increase in terminal voltage and reactive power transients caused by PSSs. The relationship between the location of selected transfer function zeros and the PSS adverse effects is demonstrated.
Keywords :
AC generators; power system stability; reactive power; transfer functions; transient analysis; transient response; generator terminal reactive power transients; generator terminal voltage transients; power system dynamics; power system stabilizers; stabilization loop; transfer function zeros; transient response; Automatic voltage control; Damping; Frequency; Poles and zeros; Power generation; Power system dynamics; Power system transients; Reactive power; Transfer functions; Transient response;