• DocumentCode
    2276080
  • Title

    Analysis of Active Power Filters operating with unbalanced loads

  • Author

    Limongi, L.R. ; Roiu, D. ; Bojoi, R. ; Tenconi, A.

  • Author_Institution
    Dept. of Electr. Eng., Politec. di Torino, Turin, Italy
  • fYear
    2009
  • fDate
    20-24 Sept. 2009
  • Firstpage
    584
  • Lastpage
    591
  • Abstract
    The aim of this paper is to perform an analysis of the shunt Active Power Filter (APF) operating with unbalanced loads. The impact of the load imbalance on the APF performance is mathematically demonstrated and validated with experimental results using a 25 kVA shunt APF prototype. The APF operation in such conditions is affected by the appearance of DC-link voltage ripple at twice the grid frequency. As consequence, the source currents become distorted and the APF performance deteriorates. Based on this fact, a new control scheme is proposed to avoid high voltage ripple in the DC link, without increasing the DC-link capacitance.
  • Keywords
    active filters; power filters; power supply quality; APF; DC-link capacitance; DC-link voltage ripple; apparent power 25 kVA; control scheme; grid frequency; load imbalance; shunt active power filter; source current; Active power filter; unbalanced load; voltage loop;
  • fLanguage
    English
  • Publisher
    ieee
  • Conference_Titel
    Energy Conversion Congress and Exposition, 2009. ECCE 2009. IEEE
  • Conference_Location
    San Jose, CA
  • Print_ISBN
    978-1-4244-2893-9
  • Electronic_ISBN
    978-1-4244-2893-9
  • Type

    conf

  • DOI
    10.1109/ECCE.2009.5316173
  • Filename
    5316173