DocumentCode :
2277161
Title :
EMTP-based black start analysis for an isolated power system
Author :
Dariani, Ali ; Rastegar, Reza
Author_Institution :
SNC Lavalin T&D, ON, Canada
fYear :
2010
fDate :
25-27 Aug. 2010
Firstpage :
1
Lastpage :
7
Abstract :
Black start studies are typically performed as part of system restoration plan when an isolated section of the grid completely shuts down and there are no neighboring systems to assist with the energization. In these cases, pre-selected units with the ability to start themselves with a well established energization plan are used to restart the system. As a case study, a power system comprising of 27 diesel generators, a 130km 230kV transmission line and a mine load is considered in terms of a black start analysis. The system is operated in isolated mode (i.e. not connected to the grid) and the black start ability is critical for energization of the system. The studies placed a strong emphasis on two main transformers at the generating substation since the inrush current imposed by these transformers was deemed to be the determining criteria for a successful black start. Detailed modeling of the transformers was performed to capture the non-linear behavior of the transformer core based on the data provided by the transformer vendor.
Keywords :
EMTP; diesel-electric generators; power grids; power system restoration; power transformers; power transmission lines; substations; EMTP; black start analysis; diesel generators; distance 130 km; generating substation; inrush current; isolated power system; power grid; power system restoration; power transmission line; transformers; voltage 230 kV; Generators; Resistance; Substations; Surge protection; Surges; Variable speed drives;
fLanguage :
English
Publisher :
ieee
Conference_Titel :
Electric Power and Energy Conference (EPEC), 2010 IEEE
Conference_Location :
Halifax, NS
Print_ISBN :
978-1-4244-8186-6
Type :
conf
DOI :
10.1109/EPEC.2010.5697254
Filename :
5697254
Link To Document :
بازگشت