• DocumentCode
    2277692
  • Title

    Study on the new method of partial discharge locating in transformer

  • Author

    Cheng, Shuyi ; Xie, Qing ; Lü, Fangcheng ; Shi, Lexian ; Yang, Haitao

  • Author_Institution
    Hebei Provincial Key Lab. of Power Transm. Equip. Security Defence, North China Electr. Power Univ., Baoding, China
  • fYear
    2012
  • fDate
    17-20 Sept. 2012
  • Firstpage
    587
  • Lastpage
    590
  • Abstract
    The quick and precise locating of partial discharge is important in eliminating the hidden faults promptly and ensuring the safety and stability of the power system. In this paper, the existing methods of PD (Partial Discharge) locating were analyzed at first, and then a PD locating method based on ultra high frequency (UHF) and ultrasonic array signals in transformer was introduced, which regards the time point of signal detected by the UHF sensor as the time benchmark to calculate the distance between PD source and ultrasonic sensor and orientate the PD source based on the modified Fast Direction of Arrival(FastDOA) algorithm by ultrasonic array signals. This algorithm expands a real sensor array into several virtual arrays of different aperture to enhance the resolution, and averages the spatial spectrum of the virtual arrays to restrain the spurious peaks. Then the orientating based on the modified FastDOA algorithm was simulated with MATLAB. The sensors were developed and the PD locating experimental platform in transformer was built at last, the experiment results of which verify the effectiveness of the proposed method.
  • Keywords
    acoustic signal processing; array signal processing; direction-of-arrival estimation; fault location; partial discharge measurement; power system faults; power system measurement; power transformers; ultrasonic measurement; UHF sensor; fast direction of arrival algorithm; hidden fault location; partial discharge; power transformer; ultrahigh frequency signal; ultrasonic array signal; Acoustics; Arrays; Multiple signal classification; Oil insulation; Partial discharges; Power transformer insulation; Partial discharge; modified FastDOA algorithm; ultra high frequency; ultrasonic array signals; virtual expanding arrays;
  • fLanguage
    English
  • Publisher
    ieee
  • Conference_Titel
    High Voltage Engineering and Application (ICHVE), 2012 International Conference on
  • Conference_Location
    Shanghai
  • Print_ISBN
    978-1-4673-4747-1
  • Type

    conf

  • DOI
    10.1109/ICHVE.2012.6357095
  • Filename
    6357095