DocumentCode :
2277947
Title :
Fault location and type identification on transmission line using a novel traveling wave method
Author :
Jianyin Liu ; Zhong Zheng
Author_Institution :
State Key Lab. for Alternate Electr. Power Syst. with Renewable Energy Sources, North China Electr. Power Univ., Beijing, China
fYear :
2012
fDate :
17-20 Sept. 2012
Firstpage :
290
Lastpage :
293
Abstract :
This paper described the principle of transmission line fault location based on traveling waves. The uncertainty of wave speed brings error to fault location based on traveling waves. The present fault location methods avoiding wave speed were based on single or double terminal traveling waves. However, invalidation or great error will occur when the attenuated waves can not be measured after refraction or reflection. The authors introduced two novel and easy-to-measure parameters, which provide a new approach to greatly improve the accuracy of fault location. The first pulse wave of fault also gives many characteristic information of the failure which was used to identify the type of failures to convenient the workers making targeted rush repair. Field measurement and calculation results are compared and the related limitations are discussed.
Keywords :
electric field measurement; fault diagnosis; fault location; power transmission faults; power transmission lines; power transmission protection; fault type identification; field measurement; pulse wave; terminal traveling wave; transmission line fault location; traveling wave uncertainty; Fault location; Grounding; Monitoring; Poles and towers; Power transmission lines; Transmission line measurements;
fLanguage :
English
Publisher :
ieee
Conference_Titel :
High Voltage Engineering and Application (ICHVE), 2012 International Conference on
Conference_Location :
Shanghai
Print_ISBN :
978-1-4673-4747-1
Type :
conf
DOI :
10.1109/ICHVE.2012.6357109
Filename :
6357109
Link To Document :
بازگشت