Title :
Experimental evaluation of PROFINET performance
Author :
Ferrari, P. ; Flammini, A. ; Marioli, D. ; Taroni, A.
Author_Institution :
Dept. of Electron. for Autom., Brescia Univ., Italy
Abstract :
In this paper PROFINET, the new industrial real-time Ethernet protocol, is considered. PROFINET has been designed to cover all sectors of distributed automation, from process control, to distributed I/O and to motion control. After an overview of Ethernet limitations, the different kinds of PROFINET are presented followed by experimental results. Authors have realized a test environment to achieve proper timing measure over a PROFINET network assembled with now available and future components. Preliminary results show that PROFINET Non-RT protocol can integrate existing fieldbus plant, whereas PROFINET RT Class 1 protocol has a good real-time behavior with cycle variability less than 10% even in high-loaded network condition.
Keywords :
field buses; local area networks; motion control; process control; protocols; PROFINET Non-RT protocol; PROFINET RT Class 1 protocol; PROFINET performance; distributed I/O; distributed automation; fieldbus plant; industrial Ethernet protocol; motion control; process control; real time Ethernet protocol; Assembly; Design automation; Ethernet networks; Field buses; Motion control; Motion planning; Process control; Protocols; Testing; Timing;
Conference_Titel :
Factory Communication Systems, 2004. Proceedings. 2004 IEEE International Workshop on
Print_ISBN :
0-7803-8734-1
DOI :
10.1109/WFCS.2004.1377739