DocumentCode :
227860
Title :
Thermal performance modeling of hybrid liquid-air cooled servers
Author :
Zeighami, Roy ; Saunders, Winston A. ; Coles, Henry ; Branton, Steve
Author_Institution :
Cisco Corp., Richardson, TX, USA
fYear :
2014
fDate :
27-30 May 2014
Firstpage :
583
Lastpage :
587
Abstract :
This paper discusses data center scale performance characterization of hybrid liquid-air cooling solutions for a full 42U rack of servers. Using data collected in a production data center at Lawrence Berkeley Laboratories, we interpret the results with a simple three parameter model which allows characterization of the major factors affecting heat recovery efficiency of the system. The model is shown to agree with a broad set of data under a variety of temperature and workload conditions. To our knowledge, this is the first large scale characterization of a hybrid cooling solution´s performance in terms relevant to data center operation. We discuss how this method can be extended to other systems for meaningful comparison of solution performance.
Keywords :
computer centres; cooling; heat recovery; network servers; thermal management (packaging); Lawrence Berkeley Laboratories; data center scale performance characterization; heat recovery efficiency; hybrid cooling solution; hybrid liquid-air cooled server; thermal performance modeling; workload condition; Heat recovery; Liquid cooling; Power measurement; Servers; Temperature measurement; Water heating; air; cooling; data center; energy reuse; liquid; power; server; water cooling;
fLanguage :
English
Publisher :
ieee
Conference_Titel :
Thermal and Thermomechanical Phenomena in Electronic Systems (ITherm), 2014 IEEE Intersociety Conference on
Conference_Location :
Orlando, FL
ISSN :
1087-9870
Type :
conf
DOI :
10.1109/ITHERM.2014.6892333
Filename :
6892333