• DocumentCode
    2280273
  • Title

    Influence of busbar geometry on AC current measurement using Rogowski coil

  • Author

    Chekurov, Y. ; Hallstrom, J.

  • Author_Institution
    MIKES-TKK, Helsinki Univ. of Technol., Helsinki
  • fYear
    2008
  • fDate
    8-13 June 2008
  • Firstpage
    542
  • Lastpage
    543
  • Abstract
    Readout of a Rogowski coil is affected by external magnetic fields e.g. from the energizing transformer and the return current conductor. The influence of these external magnetic fields on the reading of a high precision Rogowski coil was measured. The results are used to estimate the achievable uncertainty in calibration of current transformers up to 10 kA.
  • Keywords
    calibration; coils; current transformers; electric current measurement; measurement uncertainty; AC current measurement; Rogowski coil readout; busbar geometry; calibration; current transformer; external magnetic fields; high-precision Rogowski coil; measurement uncertainty; Calibration; Coils; Conductors; Current measurement; Current transformers; Geometry; Magnetic field measurement; Phase measurement; Testing; Voltage;
  • fLanguage
    English
  • Publisher
    ieee
  • Conference_Titel
    Precision Electromagnetic Measurements Digest, 2008. CPEM 2008. Conference on
  • Conference_Location
    Broomfield, CO
  • Print_ISBN
    978-1-4244-2399-6
  • Electronic_ISBN
    978-1-4244-2400-9
  • Type

    conf

  • DOI
    10.1109/CPEM.2008.4574893
  • Filename