DocumentCode :
2280538
Title :
Kalman filter used for on line monitoring and predictive maintenance system of aluminium electrolytic capacitors in UPS
Author :
Abdennadher, Karim ; Venet, Pascal ; Rojat, Gérard ; Retif, J.M. ; Rosset, Christophe
Author_Institution :
IT Bus., Emerging Technol. Dept., Schneider Electr., St. Ismier, France
fYear :
2009
fDate :
20-24 Sept. 2009
Firstpage :
3188
Lastpage :
3193
Abstract :
The electrolytic capacitor usually has the shortest span of life in the power converter. This paper presents a new low cost implementation of a real time condition monitoring and a predictive maintenance system of an electrolytic capacitor used in Uninterruptible Power Supplies (UPS). It consists of detecting the changes in real time in equivalent series resistance (ESR) and the capacitance C values of the electrolytic capacitors. The proposed method can be used in UPS where waveforms are continuously varying in amplitude, frequency and versus ambient temperature. This method has the merits of using known algorithms and only the existent resources in UPS.
Keywords :
Kalman filters; capacitor storage; condition monitoring; electrolytic capacitors; uninterruptible power supplies; Kalman filter; condition monitoring; electrolytic capacitors; equivalent series resistance; predictive maintenance; uninterruptible power supplies; Electrolytic Capacitors; Kalman filtering; Predictive Maintenance; Real Time processing; Uninterruptible Power Supplies (UPS);
fLanguage :
English
Publisher :
ieee
Conference_Titel :
Energy Conversion Congress and Exposition, 2009. ECCE 2009. IEEE
Conference_Location :
San Jose, CA
Print_ISBN :
978-1-4244-2893-9
Electronic_ISBN :
978-1-4244-2893-9
Type :
conf
DOI :
10.1109/ECCE.2009.5316418
Filename :
5316418
Link To Document :
بازگشت