• DocumentCode
    2282241
  • Title

    Auto-normalizing Phase-Locked Loop for grid-connected converters

  • Author

    Angquist, Lennart ; Bongiorno, Massimo

  • Author_Institution
    Sch. of Electr. Eng., R. Inst. of Technol., Stockholm, Sweden
  • fYear
    2009
  • fDate
    20-24 Sept. 2009
  • Firstpage
    2957
  • Lastpage
    2964
  • Abstract
    A proper synchronization algorithm is a key issue for modern grid-connected power electronic devices, especially in case of weak networks. This paper deals with a novel Phase-Locked Loop (PLL) algorithm for power electronic devices. The proposed algorithm, here named auto-normalizing PLL (AN-PLL), is able to deal with both amplitude and phase-angle changes in the measured grid voltage. Thus, the proposed concept provides a PLL control performance that is independent on the control signal amplitude. Advantages of the AN-PLL over the conventional PLL approach are highlighted. Experimental results are used to validate the dynamic performance of the proposed synchronization system.
  • Keywords
    phase locked loops; power convertors; power grids; synchronisation; autonormalizing PLL; autonormalizing phase-locked loop; control signal amplitude; grid voltage; grid-connected converters; power electronic devices; synchronization algorithm;
  • fLanguage
    English
  • Publisher
    ieee
  • Conference_Titel
    Energy Conversion Congress and Exposition, 2009. ECCE 2009. IEEE
  • Conference_Location
    San Jose, CA
  • Print_ISBN
    978-1-4244-2893-9
  • Electronic_ISBN
    978-1-4244-2893-9
  • Type

    conf

  • DOI
    10.1109/ECCE.2009.5316513
  • Filename
    5316513