Title :
A measurement system for traceable calibration of power harmonics and flicker analysers
Author :
Hammond, G. ; Budovsky, I.
Author_Institution :
Nat. Meas. Lab., CSIRO, Lindfield, NSW, Australia
Abstract :
The paper describes a precision measurement system developed at NML for traceable calibration of three-phase instruments measuring harmonics of current up to 16 A, voltage fluctuation and flicker. Current and voltage harmonics up to the 99/sup th/ and fluctuating voltages can be generated and measured with relative uncertainties close to 1/spl times/10/sup -5/.
Keywords :
calibration; electric current measurement; electromagnetic compatibility; fluctuations; harmonic analysis; measurement uncertainty; network analysers; power system harmonics; power system measurement; voltage measurement; 16 A; EMC; current harmonics measurement; electromagnetic compatibility; fluctuating voltages; power flicker analysers; power harmonics analysers; precision measurement system; relative measurement uncertainty; three-phase instruments; traceable calibration; voltage flicker; voltage fluctuation; voltage harmonics; Australia; Calibration; Displays; Electromagnetic compatibility; Harmonic analysis; IEC; Power measurement; Power system harmonics; Testing; Voltage fluctuations;
Conference_Titel :
Precision Electromagnetic Measurements, 2002. Conference Digest 2002 Conference on
Conference_Location :
Ottawa, Ontario, Canada
Print_ISBN :
0-7803-7242-5
DOI :
10.1109/CPEM.2002.1034810