• DocumentCode
    2282740
  • Title

    A measurement system for traceable calibration of power harmonics and flicker analysers

  • Author

    Hammond, G. ; Budovsky, I.

  • Author_Institution
    Nat. Meas. Lab., CSIRO, Lindfield, NSW, Australia
  • fYear
    2002
  • fDate
    16-21 June 2002
  • Firstpage
    238
  • Lastpage
    239
  • Abstract
    The paper describes a precision measurement system developed at NML for traceable calibration of three-phase instruments measuring harmonics of current up to 16 A, voltage fluctuation and flicker. Current and voltage harmonics up to the 99/sup th/ and fluctuating voltages can be generated and measured with relative uncertainties close to 1/spl times/10/sup -5/.
  • Keywords
    calibration; electric current measurement; electromagnetic compatibility; fluctuations; harmonic analysis; measurement uncertainty; network analysers; power system harmonics; power system measurement; voltage measurement; 16 A; EMC; current harmonics measurement; electromagnetic compatibility; fluctuating voltages; power flicker analysers; power harmonics analysers; precision measurement system; relative measurement uncertainty; three-phase instruments; traceable calibration; voltage flicker; voltage fluctuation; voltage harmonics; Australia; Calibration; Displays; Electromagnetic compatibility; Harmonic analysis; IEC; Power measurement; Power system harmonics; Testing; Voltage fluctuations;
  • fLanguage
    English
  • Publisher
    ieee
  • Conference_Titel
    Precision Electromagnetic Measurements, 2002. Conference Digest 2002 Conference on
  • Conference_Location
    Ottawa, Ontario, Canada
  • Print_ISBN
    0-7803-7242-5
  • Type

    conf

  • DOI
    10.1109/CPEM.2002.1034810
  • Filename
    1034810