DocumentCode :
2282898
Title :
Development of a high precision AC standard shunt for AC power measurement
Author :
Tsuchiyama, T. ; Tadokoro, T.
Author_Institution :
Japan Electr. Meters Inspection Corp., Tokyo, Japan
fYear :
2002
fDate :
16-21 June 2002
Firstpage :
254
Lastpage :
255
Abstract :
The authors developed an AC standard shunt (rated 10 A, 0.1 /spl Omega/), for frequencies from DC to 10 kHz, which has a highly stable resistance value and small phase angle error. By using this AC standard shunt, AC power and current may be measured with high accuracy. The stability and uncertainty of the shunt correspond to 3 ppm with regard to AC power measurement at 1 kHz.
Keywords :
circuit stability; electric current measurement; measurement errors; measurement standards; measurement uncertainty; power measurement; resistors; 0 Hz to 10 kHz; 0.1 ohm; 1 kHz; 10 A; AC current measurement accuracy; AC high precision standard shunts; AC power measurement; phase angle error; resistance value stability; resistance value uncertainty; resistors; shunt frequency measurement range; shunt rating; Capacitance; Circuit stability; Eddy currents; Inductance; Measurement standards; Power measurement; Printed circuits; Resistors; Standards development; Voltage;
fLanguage :
English
Publisher :
ieee
Conference_Titel :
Precision Electromagnetic Measurements, 2002. Conference Digest 2002 Conference on
Conference_Location :
Ottawa, Ontario, Canada
Print_ISBN :
0-7803-7242-5
Type :
conf
DOI :
10.1109/CPEM.2002.1034818
Filename :
1034818