DocumentCode :
2283005
Title :
Three phase grid connected anti-islanding controller based on distributed generation interconnection
Author :
Abdolrasol, Maher G M ; Mekhilef, Saad
Author_Institution :
Dept. of Electr. Eng., Univ. of Malaya, Kuala Lumpur, Malaysia
fYear :
2010
fDate :
Nov. 29 2010-Dec. 1 2010
Firstpage :
717
Lastpage :
722
Abstract :
This paper proposes three phase grid connected anti-islanding controller based on distributed generation interconnection. This method is a combination of two detection methods namely active and passive. Firstly, Active islanding detection generates disturbances at the output of the distributed generation by use of Positive feedback and Continuous feedback signal injection which is based on DQ implementation. Secondly, passive islanding detection method is based on measuring the system parameters such as voltage, frequency, active and reactive power and total harmonic distortion (THD). This method use three phase RLC load and compares the performance of the technique with and without the anti islanding controller. Islanding conditions are simulated and verified with full analysis simulation and experimental result.
Keywords :
distributed power generation; feedback; load (electric); power distribution control; power grids; power system interconnection; DQ implementation; RLC load; active islanding detection; antiislanding controller; continuous feedback signal injection; distributed generation interconnection; passive islanding detection; positive feedback; three phase grid; anti-islanding; distributed generation; non detection zone;
fLanguage :
English
Publisher :
ieee
Conference_Titel :
Power and Energy (PECon), 2010 IEEE International Conference on
Conference_Location :
Kuala Lumpur
Print_ISBN :
978-1-4244-8947-3
Type :
conf
DOI :
10.1109/PECON.2010.5697673
Filename :
5697673
Link To Document :
بازگشت