DocumentCode
2283005
Title
Three phase grid connected anti-islanding controller based on distributed generation interconnection
Author
Abdolrasol, Maher G M ; Mekhilef, Saad
Author_Institution
Dept. of Electr. Eng., Univ. of Malaya, Kuala Lumpur, Malaysia
fYear
2010
fDate
Nov. 29 2010-Dec. 1 2010
Firstpage
717
Lastpage
722
Abstract
This paper proposes three phase grid connected anti-islanding controller based on distributed generation interconnection. This method is a combination of two detection methods namely active and passive. Firstly, Active islanding detection generates disturbances at the output of the distributed generation by use of Positive feedback and Continuous feedback signal injection which is based on DQ implementation. Secondly, passive islanding detection method is based on measuring the system parameters such as voltage, frequency, active and reactive power and total harmonic distortion (THD). This method use three phase RLC load and compares the performance of the technique with and without the anti islanding controller. Islanding conditions are simulated and verified with full analysis simulation and experimental result.
Keywords
distributed power generation; feedback; load (electric); power distribution control; power grids; power system interconnection; DQ implementation; RLC load; active islanding detection; antiislanding controller; continuous feedback signal injection; distributed generation interconnection; passive islanding detection; positive feedback; three phase grid; anti-islanding; distributed generation; non detection zone;
fLanguage
English
Publisher
ieee
Conference_Titel
Power and Energy (PECon), 2010 IEEE International Conference on
Conference_Location
Kuala Lumpur
Print_ISBN
978-1-4244-8947-3
Type
conf
DOI
10.1109/PECON.2010.5697673
Filename
5697673
Link To Document