DocumentCode :
2283712
Title :
The calculate of nonlinear and anisotropic electric field in valve side winding of converter transformer
Author :
Li, Yan ; Li, Xiaohui ; Du, Jianping ; Li, Longnv ; Li, Dongxue
Author_Institution :
Nat. Eng. Res. Center for Rare Earth Permanent Magn. Machine, Shenyang Univ. of Technol., Shenyang, China
fYear :
2011
fDate :
20-23 Aug. 2011
Firstpage :
1
Lastpage :
4
Abstract :
Oil-immersed insulating material has an anisotropic and nonlinear conductivity, so the direct current (dc) electric field calculation should take these factors into consideration. In this paper, a new calculating method based on ANSYS secondary development technology is proposed. Then, the nonlinear and anisotropic dc electric field is calculated, considering electrical stress and temperature impact on conductivity. The results show that the electric field distribution calculation is very different if considering or not considering these factors. Therefore, the converter transformer insulation design should be calculate as anisotropic and nonlinear field.
Keywords :
power transformer insulation; transformer oil; transformer windings; ANSYS secondary development technology; anisotropic electric field; converter transformer insulation design; electric field distribution; electrical stress; nonlinear electric field; oil-immersed insulating material; valve side winding; Conductivity; Electric fields; Oil insulation; Power transformer insulation; Steady-state; Stress; Windings;
fLanguage :
English
Publisher :
ieee
Conference_Titel :
Electrical Machines and Systems (ICEMS), 2011 International Conference on
Conference_Location :
Beijing
Print_ISBN :
978-1-4577-1044-5
Type :
conf
DOI :
10.1109/ICEMS.2011.6073990
Filename :
6073990
Link To Document :
بازگشت