DocumentCode
2283855
Title
Axial vibration analysis of power transformer active part under short-circuit
Author
Li, Yan ; Zhou, Wei ; Jing, Yongteng ; Sun, Xin
Author_Institution
Res. Instn. of Special Electr. Machines, Shenyang Univ. of Technol., Shenyang, China
fYear
2011
fDate
20-23 Aug. 2011
Firstpage
1
Lastpage
4
Abstract
Based on 500kV power transformer, according to the mass-spring system model for the axial vibration of power transformer winding and its nonlinear characteristics, a calculation model is simplified, the modal simulation system of power transformer active part, which composes of core, windings, tensile plates and clamp frames is established, the natural frequencies and vibration modal in different levels of axial pre-compression of transformer active part are calculated, the relations between the changes of axial pre-compression and axial vibration natural frequencies on transformer active part are investigated. Meanwhile, the active part vibration caused by axial short-circuit forces of windings under short-circuit conditions is analyzed.
Keywords
compensation; cores; power transformers; short-circuit currents; transformer windings; vibrations; axial pre-compression; axial vibration analysis; clamp frames; core; mass-spring system model; modal simulation system; power transformer active part; short-circuit current; tensile plates; transformer winding; vibration modal; voltage 500 kV; Equations; Finite element methods; Mathematical model; Power transformer insulation; Vibrations; Windings;
fLanguage
English
Publisher
ieee
Conference_Titel
Electrical Machines and Systems (ICEMS), 2011 International Conference on
Conference_Location
Beijing
Print_ISBN
978-1-4577-1044-5
Type
conf
DOI
10.1109/ICEMS.2011.6073998
Filename
6073998
Link To Document