Title :
Measurement of conductor temperature of power cable by optical fiber sensor
Author :
Ichino, T. ; Suzuki, T. ; Wada, T. ; Sadahiro, T.
Author_Institution :
Chubu Electric Power Co. Inc., Nagoya, Japan
Abstract :
We conducted temperature measurements on the feeder cables of a substation for power distribution by using a distributed optical fiber sensor. As a result we confirmed that the hot point of a conduit with multiple lines installed can be determined with ease. Moreover, our calculations resulted in a maximum conductor temperature of 70°C, which confirms that there still remains a tolerance of approximately 20°C. Hereinafter, we will continue with our study in pursuit of a method that would allow to compute allowable currents by using the sensor mentioned above
Keywords :
power cable testing; conductor temperature measurement; conduit; distributed optical fiber sensor; hot point; multiple line; power cable; substation;
Conference_Titel :
Dielectric Materials, Measurements and Applications, Seventh International Conference on (Conf. Publ. No. 430)
Conference_Location :
Bath
Print_ISBN :
0-85296-670-9
DOI :
10.1049/cp:19961046