Title :
Three level STATCOM Based Power Quality Solution for a 4 MW Induction Furnace
Author :
Unnikrishnan AK ; Joseph, Aby ; Subhash Joshi, T.G.
Author_Institution :
Centre for Dev. of Adv. Comput., Trivandrum
Abstract :
The paper explains the power quality study conducted in a 4 MW mini steel plant, having fault level of 250 MVA, to investigate the critical electrical problems caused by the harmonics and the development of a STATCOM as a solution for harmonic mitigation. A 500 Kvar STATCOM is realized with a current controlled three level voltage source converter (VSC). The hardware configuration and the control strategy have been dealt in detail. Site installation and experimental results verifying STATCOM´s performance are also presented.
Keywords :
active networks; furnaces; power supply quality; power system harmonics; static VAr compensators; 4 MW; STATCOM; current controlled voltage source converter; harmonic mitigation; induction furnace; power quality study; steel plant; Active filters; Automatic voltage control; Furnaces; Passive filters; Power harmonic filters; Power quality; Power system harmonics; Pulse width modulation converters; Steel; Switching converters; Digital Signal Processor (DSP); IEEE 519-1992 Std.; Power Quality (PQ); Pulse Width Modulation (PWM); STATCOM; Three level converter; Total Demand Distortion (TDD); Unit vector; Voltage Source Converter (VSC); induction furnace;
Conference_Titel :
Power Electronics, Drives and Energy Systems, 2006. PEDES '06. International Conference on
Conference_Location :
New Delhi
Print_ISBN :
0-7803-9772-X
Electronic_ISBN :
0-7803-9772-X
DOI :
10.1109/PEDES.2006.344242