DocumentCode :
2287218
Title :
Investigation of factors affecting the sustainability of arcs below 250V
Author :
Lang, Mike ; Jones, Ken
Author_Institution :
Mersen, Newburyport, MA, USA
fYear :
2011
fDate :
9-13 Oct. 2011
Firstpage :
1
Lastpage :
9
Abstract :
Recent testing with various electrode configurations and insulating barriers suggests that 250V equipment omitted from arc flash hazard analyses has the potential for burn injury. Research into the sustainability of arcs at these voltages shows assumptions about the magnitude of these hazards need to be revised. This research enhanced the work of previous efforts by focusing on the sustainability of arcs with fault currents lower than 10kA. Gap lengths between electrodes, electrode shape, electrode material and voltage variations were studied for their effects on arc sustainability. A modified barrier design, representative of the space around panelboard bus bars was also studied.
Keywords :
arcs (electric); busbars; electrodes; flashover; hazards; insulation; arc flash hazard; arc sustainability; burn injury; electrode configurations; electrode material; electrode shape; fault currents; gap lengths; insulating barriers; panelboard bus bars; voltage variations; Copper; Electrodes; Ignition; Testing; Arc fault sustainability; arc flash hazard testing; effect of insulating barriers; plasma; terminated vertical conductors; terminated vertical electrodes; vertical conductors; vertical electrodes;
fLanguage :
English
Publisher :
ieee
Conference_Titel :
Industry Applications Society Annual Meeting (IAS), 2011 IEEE
Conference_Location :
Orlando, FL
ISSN :
0197-2618
Print_ISBN :
978-1-4244-9498-9
Type :
conf
DOI :
10.1109/IAS.2011.6074423
Filename :
6074423
Link To Document :
بازگشت