• DocumentCode
    2287218
  • Title

    Investigation of factors affecting the sustainability of arcs below 250V

  • Author

    Lang, Mike ; Jones, Ken

  • Author_Institution
    Mersen, Newburyport, MA, USA
  • fYear
    2011
  • fDate
    9-13 Oct. 2011
  • Firstpage
    1
  • Lastpage
    9
  • Abstract
    Recent testing with various electrode configurations and insulating barriers suggests that 250V equipment omitted from arc flash hazard analyses has the potential for burn injury. Research into the sustainability of arcs at these voltages shows assumptions about the magnitude of these hazards need to be revised. This research enhanced the work of previous efforts by focusing on the sustainability of arcs with fault currents lower than 10kA. Gap lengths between electrodes, electrode shape, electrode material and voltage variations were studied for their effects on arc sustainability. A modified barrier design, representative of the space around panelboard bus bars was also studied.
  • Keywords
    arcs (electric); busbars; electrodes; flashover; hazards; insulation; arc flash hazard; arc sustainability; burn injury; electrode configurations; electrode material; electrode shape; fault currents; gap lengths; insulating barriers; panelboard bus bars; voltage variations; Copper; Electrodes; Ignition; Testing; Arc fault sustainability; arc flash hazard testing; effect of insulating barriers; plasma; terminated vertical conductors; terminated vertical electrodes; vertical conductors; vertical electrodes;
  • fLanguage
    English
  • Publisher
    ieee
  • Conference_Titel
    Industry Applications Society Annual Meeting (IAS), 2011 IEEE
  • Conference_Location
    Orlando, FL
  • ISSN
    0197-2618
  • Print_ISBN
    978-1-4244-9498-9
  • Type

    conf

  • DOI
    10.1109/IAS.2011.6074423
  • Filename
    6074423