• DocumentCode
    2293542
  • Title

    Application of surge arresters to a 115-kV circuit

  • Author

    Short, T.A. ; Warren, C.A. ; Burke, J.J. ; Burns, C.W. ; Godlewski, J.R. ; Graydon, F., Jr. ; Morosini, H.

  • Author_Institution
    Power Technol. Inc., Schenectady, NY, USA
  • fYear
    1996
  • fDate
    15-20 Sep 1996
  • Firstpage
    276
  • Lastpage
    282
  • Abstract
    Momentary interruptions caused by lightning were a severe problem for a Champion International paper mill in upstate New York. Following a detailed investigation, the Niagara Mohawk Power Corporation (NMPC) installed line surge arresters to the supply circuit to eliminate lightning-caused interruptions. The paper mill is supplied by a 115-kV circuit which was characterized by low insulation level and poor grounding. Lightning arresters were found to be the best solution. Extensive line performance monitoring of the circuit performed before and after the arresters were installed has provided some valuable information. The arresters have successfully eliminated the lightning-caused interruptions
  • Keywords
    arresters; industrial power systems; lightning protection; paper industry; power system protection; 115 kV; Champion International paper mill; New York; Niagara Mohawk Power Corporation; lightning protection; lightning-caused interruptions elimination; line performance monitoring; low insulation level; poor grounding; supply circuit; surge arresters application; Arresters; Circuits; Insulation; Lightning; Milling machines; Monitoring; Paper mills; Poles and towers; Power quality; Surge protection;
  • fLanguage
    English
  • Publisher
    ieee
  • Conference_Titel
    Transmission and Distribution Conference, 1996. Proceedings., 1996 IEEE
  • Conference_Location
    Los Angeles, CA
  • Print_ISBN
    0-7803-3522-8
  • Type

    conf

  • DOI
    10.1109/TDC.1996.545947
  • Filename
    545947