Energy stress on transmission line arresters considering the total lightning charge distribution
Author
Stenström, L. ; Lundquist, J.
Author_Institution
ABB Switchgear, Ludvika, Sweden
fYear
1996
fDate
15-20 Sep 1996
Firstpage
302
Lastpage
306
Abstract
Transmission line arresters may be subjected to high energy stresses caused by lighting. Calculations of energy stresses were carried out for a typical line arrester installation. Three line configurations with different degrees of shielding efficiency were used for the study. The primary statistical parameter was the charge of the flash, including multiple strokes. The effect of stroke current magnitude was also investigated. The calculated results were compared with energy stresses in standardized tests on surge arresters
Keywords
arresters; electric charge; lightning protection; power system protection; power transmission lines; shielding; energy stress; multiple strokes; shielding efficiency; standardized tests; statistical parameter; stroke current magnitude; surge arresters; total lightning charge distribution; transmission line arresters; Arresters; Circuits; Grounding; Lightning; Poles and towers; Stress; Substations; Surges; Transmission lines; Wires;