• DocumentCode
    2300063
  • Title

    Negative sequence relay protection for blown high side transformer fuse detection

  • Author

    Hannah, A.

  • Author_Institution
    Southwest Arkansas Electr. Cooperative Corp., AR
  • fYear
    1998
  • fDate
    26-28 Apr 1998
  • Lastpage
    42376
  • Abstract
    Single phasing conditions caused by blown fuses on the primary of a delta-wye substation power transformer can create problems for electric utilities and the customers they serve. Sustained low voltages present during these conditions create problems for three-phase and single-phase loads. This paper outlines a method of detecting these single phase conditions using negative sequence relay technology. The paper also summarizes a method of isolating customer loads from the substation bus to prevent damage to customer appliances
  • Keywords
    electric fuses; electricity supply industry; load (electric); overvoltage protection; power system protection; power system relaying; power transformer protection; relay protection; transformer substations; blown fuse detection; customer load isolation; delta-wye substation power transformer; electric utilities; negative sequence relay protection; single-phase loads; three-phase loads; Fuses; Home appliances; Isolation technology; Low voltage; Phase detection; Power industry; Power transformers; Protective relaying; Relays; Substations;
  • fLanguage
    English
  • Publisher
    ieee
  • Conference_Titel
    Rural Electric Power Conference, 1998. Papers Presented at the 42nd Annual Conference
  • Conference_Location
    St. Louis, MO
  • Print_ISBN
    0-7803-4459-6
  • Type

    conf

  • DOI
    10.1109/REPCON.1998.666953
  • Filename
    666953