Abstract :
This paper discusses the maximum ground fault resistance, which can be tolerated by a distance relay with Quadrilateral characteristic applied at the source node of a distribution feeder. This resistance is defined as the boundary fault resistance which is the boundary of the distance relay correct discrimination between in-zone and out-of-zone faults. The robustness criterion is defined based on the boundary fault resistance. In order to achieve this, the related equations are presented and the boundary fault resistance curve is introduced. The variation of the boundary fault resistance curve and the robustness criterion is investigated due to the changes in the power system conditions.
Keywords :
fault diagnosis; power system faults; power transmission lines; relays; boundary fault resistance; distance relay; distribution feeders; quadrilateral characteristic; robustness criterion; Electric resistance; Electrical resistance measurement; Impedance measurement; Power system dynamics; Power system faults; Power system measurements; Power system protection; Power system relaying; Protective relaying; Robustness; Arcing Faults; Boundary fault resistance; Distance protection; Distribution feeder; Fault resistance; Robustness criterion;
fLanguage :
English
Publisher :
ieee
Conference_Titel :
Power System Technology and IEEE Power India Conference, 2008. POWERCON 2008. Joint International Conference on
Conference_Location :
New Delhi
Print_ISBN :
978-1-4244-1763-6
Electronic_ISBN :
978-1-4244-1762-9
Type :
conf
DOI :
10.1109/ICPST.2008.4745269
Filename :
4745269
Link To Document :
بازگشت