• DocumentCode
    2314950
  • Title

    A Comparison of Voltage Stability Indices for Placing Shunt FACTS Controllers

  • Author

    Phadke, A.R. ; Bansal, S.K. ; Niazi, K.R.

  • Author_Institution
    Malviya Nat. Inst. of Technol., Jaipur
  • fYear
    2008
  • fDate
    16-18 July 2008
  • Firstpage
    939
  • Lastpage
    944
  • Abstract
    Location of shunt compensation devices is important for the enhancement of the voltage stability for practical power systems. This paper presents a comparison of several voltage stability indices in electric power system to identify the weakest bus/ area of the system. Shunt FACTS controller is introduced at the weakest bus in IEEE 14-bus test system and its effectiveness is assessed by comparing voltage profile and loading margin enhancement. Various line stability indices are also compared with and without shunt FACTS controller. It is shown that the best location for reactive power compensation for improving static voltage stability margin is the "weakest bus" of the system.
  • Keywords
    compensation; flexible AC transmission systems; power system stability; power transmission control; reactive power; FACTS controller; IEEE 14-bus test system; electric power system; practical power system; reactive power compensation; shunt compensation device; static voltage stability; Capacitors; Control systems; Modal analysis; Power system stability; Reactive power; Reactive power control; Stability analysis; Steady-state; System testing; Voltage control; FACTS controllers; Static voltage stability; loading margin; placement;
  • fLanguage
    English
  • Publisher
    ieee
  • Conference_Titel
    Emerging Trends in Engineering and Technology, 2008. ICETET '08. First International Conference on
  • Conference_Location
    Nagpur, Maharashtra
  • Print_ISBN
    978-0-7695-3267-7
  • Electronic_ISBN
    978-0-7695-3267-7
  • Type

    conf

  • DOI
    10.1109/ICETET.2008.30
  • Filename
    4580037