Abstract
A large number of the power transformers in service today have reached an age of 30 years or more. Thus, they might have reached a critical condition. The ageing rate is determined by the thermal load and to a considerable degree also by the water content in the solid insulation material. For an estimation of the total amount of water in a transformer, knowledge about the typical profile of the water content in a transformer as it is created after a certain time of operation is extremely helpful. The decision about drying of the active part of a transformer as a value conserving measure is based finally on the total amount of water in a transformer. In This work results of the investigation of the profiles of water content and degree of polymerisation before and after performing the active part drying procedure will be presented based on data from a 31.5 MVA transformer (110 kV) manufactured in 1955.
Keywords
ageing; polymerisation; power transformer insulation; water; 110 KV; 31.5 MVA; ageing; polymerisation; power transformer insulation; solid insulation material; thermal load; water; Dielectrics and electrical insulation; Oil insulation; Petroleum; Plastic insulation; Polymers; Power transformer insulation; Power transformers; Solids; Thermal stresses; Water conservation;
fLanguage
English
Publisher
ieee
Conference_Titel
Electrical Insulation, 2004. Conference Record of the 2004 IEEE International Symposium on
ISSN
1089-084X
Print_ISBN
0-7803-8447-4
Type
conf
DOI
10.1109/ELINSL.2004.1380475
Filename
1380475
Link To Document