DocumentCode :
2317022
Title :
Harmonics at the utility-industrial interface: a real-world example
Author :
Almonte, Robert L. ; Ashley, A.Wayne
Author_Institution :
Amoco Production Co., Tulsa, OK, USA
fYear :
1994
fDate :
12-14 Sep 1994
Firstpage :
63
Lastpage :
71
Abstract :
This paper describes the application of 5th and 7th harmonic filters to an oil gathering and processing facility substation to reduce total harmonic voltage distortion on the local utility system to within IEEE-519 recommended limits. The authors describe harmonic amplification, harmonic analysis and 25 kV bulk filter design, filter construction and installation, and filter energisation results
Keywords :
harmonic distortion; industrial power systems; petroleum industry; power filters; power system harmonics; substations; 25 kV; 5th harmonic filter; 7th harmonic filter; IEEE-519 recommended limits; bulk filter design; filter construction; filter energisation results; filter installation; harmonic amplification; harmonic analysis; harmonic voltage distortion reduction; oil gathering facility; oil processing facility; substation; utility-industrial interface; Distortion measurement; Guidelines; Harmonic distortion; Petroleum; Power harmonic filters; Power system harmonics; Substations; Total harmonic distortion; Variable speed drives; Voltage;
fLanguage :
English
Publisher :
ieee
Conference_Titel :
Petroleum and Chemical Industry Conference, 1994. Record of Conference Papers., Institute of Electrical and Electronics Engineers Incorporated Industry Applications Society 41st Annual
Conference_Location :
Vancouver, BC
Print_ISBN :
0-7803-1987-7
Type :
conf
DOI :
10.1109/PCICON.1994.347631
Filename :
347631
Link To Document :