Title :
Statistical analysis of large amount of power cables diagnostic data
Author :
Cichecki, Piotr ; Gulski, Edward ; Smit, J.J. ; Jongen, R. ; Petzold, Frank
Author_Institution :
Delft Univ. of Technol., Delft
Abstract :
In this contribution statistical analysis were applied to evaluate condition of serviced aged MV power cables systems. Analysis were based on large number of diagnostic data as obtained from the on-site inspections of 89 mass insulated power cables, 26 XLPE insulated power cables and 126 mixed-insulated power cable. Statistical analysis input data was represented with several diagnostic parameters regarding to partial discharges phenomenon (PD). Investigated parameters were obtained with application of damped AC (DAC) diagnostic system during on-site tests. After a survey of all relevant parameters describing condition of the particular cable system components, sub-groups of different cable accessories were created (e.g. joints, termination, insulation types) For proper interpretation of collected data related to cable insulation condition as well as different accessories condition, categorization based on such diagnostic parameters e.g. PDIV (partial discharge inception voltage), PD occurrence, and PD mappings was assumed. Moreover investigated statistically PD parameters were employed to estimate experience norms and measuring criteria. Based on knowledge rules and estimated statistically norms example of so called ldquoexperimental condition indexrdquo was used to indicate overall condition of discussed MV power cables systems.
Keywords :
inspection; partial discharges; power cable insulation; statistical analysis; XLPE insulated power cables; cable insulation condition; damped AC diagnostic system; mass insulated power cables; mixed-insulated power cable; on-site inspections; partial discharge inception voltage; partial discharges phenomenon; power cables diagnostic data; statistical analysis; Aging; Cable insulation; Communication cables; Inspection; Partial discharges; Power cables; Statistical analysis; System testing; Termination of employment; Voltage; Condition index; cable insulation; damped AC; diagnostic data analysis; partial discharges; statistical analysis;
Conference_Titel :
Condition Monitoring and Diagnosis, 2008. CMD 2008. International Conference on
Conference_Location :
Beijing
Print_ISBN :
978-1-4244-1621-9
Electronic_ISBN :
978-1-4244-1622-6
DOI :
10.1109/CMD.2008.4580212